Menu Description SW2
pressing
(SPEED)
LD7 status LD8
flashing
1 Anti-wind once
Enabled ON
Disabled OFF
Flashing
once
2 Reversing stroke twice
Enabled ON
Disabled OFF
Flashing
twice
3 Soft-Touch 3 times
Enabled ON
Disabled OFF
Flashing
3 times
4 Pre-flashing 4 times
Enabled ON
Disabled OFF
Flashing
4 times
5
Leaf opening
delay
5 times
Enabled ON ( 5 sec.)
Disabled OFF
Flashing
5 times
6
Leaf closing
delay*
( Default 10 s)
6 times
ON (SW3 pressing)
OFF (no pressure)
Flashing
6 times
7
Pause time*
(Default 30 s)
7 times
ON (SW3 pressing)
OFF (no pressure)
Flashing
7 times
6.3.3 PROGRAMMING THE LOGIC
Repeatedly press the SW3 push-button to select one of the 7
programming logics available.
The selected logic is signaled by the LD7 LED.
The number of flashings corresponds to the number of the selected
logic:
(default settings in bold)
3. From now on, until next open impulse, the pause time is
counted.
4. Open impulse ---> Pause time acquisition and start of leaf
2 closing movement.
5. Open impulse ---> leaf 2 decelerated closure and start of
the search for leaf 2 closing limit stop.
- if the limit stop is detected, it is set as leaf 2 stop point and
leaf 1 starts to close.
(*) if an open command is detected, it is set as leaf 2 stop
point and leaf 1 starts to close.
6. Open impulse --->leaf 1 decelerated closure and start of
the search for leaf 1 closing limit stop.
- if the limit stop is detected, it is set as leaf 1 closing stop
point.
(*) if an open command is detected, it is set as leaf 1 closing
stop point.
If the SETUP procedure is performed correctly, the LD4 and
LD5 LEDs turn off at the end. Otherwise the procedure ends by
asking a new SETUP with flashing LEDs.
To eliminate decelerated opening and closing, send
2 consecutive open impulses to determine the opening
and closing stop point, otherwise have the leaf find
the opening and closing limit stop if you want to use
the limit stop facility.
With the MANUAL SETUP the decelerated
spaces, the leaf closing delay and the pause
time are manually set on the board during
setup. You can modify them without repeating
the setup procedure by using the 2nd level
programming.
ON
OFF
Logic Description
SW3 pressing
(LOGIC)
LD7 flashing
A Logic A (Automatic) once Flashing once
E Semi-automatic twice Flashing twice
AP
Step-by-step
automatic
3 times Flashing 3 times
EP Step-by-step
semi-automatic
4 times Flashing 4 times
A1 Automatic 1 5 times Flashing 5 times
b Semi-automatic “b” 6 times Flashing 6 times
c Dead man 7 times Flashing 7 times
6.3.4 SECOND LEVEL PROGRAMMING -
ADVANCED FUNCTIONS
To enter the 2nd level menu, press the SW2 SPEED push-button
for more than 2.5 seconds.
Both SETUP LEDs light on with steady beam. In this mode, the
SPEED key has the menu scrolling function. You can scroll the
menu by pressing it the same number of times shown for the
parameter.
The different menus are identified by the number of flashing
of LD8.
The LOGIC key is used to set the parameter value. You can
exit the 2nd level menu by pressing the SPEED key for 2.5
seconds.
(default settings in bold)
With menus 6 and 7, keep the LOGIC push-
button pressed until reaching the time to be set.
The t i me c an be s e t be twee n 0 an d
4.25 minutes.
*
ENGLISH