OPERATING LOGIC
DS 1: SW 1 - SW 2 - SW 3
LOGIC SW 1 SW 2 SW 3
PAUSE
TIME
DESCRIPTION
E (default)
Semiautomatic
OFF OFF OFF NO
One command opens, the next one closes. A command
during opening stops the gate
A
Automatic
ON ON ON
0 - 4
min
One command opens, waits for the pause time an then
closes automatically
S
Security
OFF OFF ON
0-4
min
One command opens, waits for the pause time and then
closes automatically. If the closing safety is activated or
another command is given during the pause time it closes.
A maintained open command will not hold the gate open
EP
Semiautomatic
step by step
OFF ON OFF NO
One command opens, the next one closes. During the mo-
vement a command stops the gate
AP
Automatic
step by step
OFF ON ON
0-4
min
One command opens, waits for the pause time and then
closes automatically. A command during the pause time
holds the gate open
SP
Security
step by step
ON OFF OFF
0-4
min
One command opens, waits for the pause time and then
closes automatically. If the closing safety is activated during
pause time the gate closes in 5 s. A command during pau-
se time holds open the gate
B
Manned Pulsed
ON OFF ON NO
An open A command opens the gate, an open B com-
mand closes the gate
C
Manned Constant
ON ON OFF NO
Holding open A active opens the gate, holding Open B acti-
ve closes the gate
For more details on the operating logics please refer to Chapter 11 - Function Logics
DIP SWITCH DS1 SETTINGS FOR OPERATING LOGIC
4. PROGRAMMING
17