Power supplies
POWER SUPPLIES
Non-regenerative power supplies
2.
39
DDS
HARDWARE
Ref.1310
PS-25B4. Connector description
The non-regenerative power supply PS-25B4 has the following connectors:
F. H2 /7
Connectors of the PS-25B4 power supply.
1. Power connector for the three-phase mains.
2. Power connector for the external Ballast resistor connection.
3. Ground connection for the mains cable.
4. Power Bus supplying power to the drive modules through metal bars.
X1. Connector for inter-module communication.
X2. Connector for the basic control signals.
X3. Input connector supplying from mains to the auxiliary power supply integrated into the module. The
mains power is received through it. It admits a voltage between 400 and 460 V AC.
X4. Output connector of the auxiliary 24 V DC power supply integrated into the module.
X5. Output connector of the auxiliary 24 V DC power supply integrated into the module.
X6. Output connector of the auxiliary 24 V DC power supply integrated into the module.
X3.
3.
1.
X1.
X4.
X5.
X6.
2.
4.
X2.
CAUTION. AC touch current
greater than 3.5 mA. Install
ground wire of at least 10 mm²
Cu or 16 mm² Al.