Drives
3.
Ref.1912
· 147 ·
DDS
HARDWARE
For a switching frequency fc = 8 kHz
F. H3/91
Current derating on ·ACD|CMC 2.50· drives for fc = 4 kHz.
F. H3/92
Current derating on ·ACD|CMC 1.08· drives for fc = 8 kHz.
F. H3/93
Current derating on ·ACD|CMC 1.15· drives for fc = 8 kHz.
F. H3/94
Current derating on ·ACD|CMC 1.25· drives for fc = 8 kHz.
F. H3/95
Current derating on ·ACD|CMC 2.35· drives for fc = 8 kHz.
35 40 55 60
I (Arms)
Tambient
°C (°F)
45 50
(95)
(104)
(113) (122) (131) (140)
20
In
22
24
26
ACD|CMC 2.50
T ambient In
° C ° F A
35 95 25.0
40 104 25.0
45 113 25.0
50 122 23.8
55 131 22.1
60 140 20.2
35 40 55 60
4
I (Arms)
Tambient
°C (°F)
45 50
(95)
(104)
(113) (122) (131) (140)
0
2
6
In
ACD|CMC 1.08
T ambient In
° C ° F A
35 95 4.0
40 104 4.0
45 113 4.0
50 122 3.7
55 131 3.2
60 140 2.7
35 40 55 60
7
I (Arms)
Tambient
°C (°F)
45 50
(95)
(104)
(113) (122) (131) (140)
6
8 In
ACD|CMC 1.15
T ambient In
° C ° F A
35 95 7.5
40 104 7.5
45 113 7.5
50 122 6.9
55 131 6.4
60 140 5.9
35 40 55 60
9
I (Arms)
Tambient
°C (°F)
45 50
(95)
(104)
(113) (122) (131) (140)
8
10
In
ACD|CMC 1.25
T ambient In
° C ° F A
35 95 9.5
40 104 9.5
45 113 9.5
50 122 9.0
55 131 8.5
60 140 7.9
35 40 55 60
16
I (Arms)
Tambient
°C (°F)
45 50
(95)
(104)
(113) (122) (131) (140)
15
17
In
18
ACD|CMC 2.35
T ambient In
° C ° F A
35 95 17.5
40 104 17.5
45 113 17.5
50 122 17.0
55 131 15.9
60 140 14.9