EasyManuals Logo

Fagor DDS Series User Manual

Fagor DDS Series
406 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #318 background imageLoading...
Page #318 background image
Functional safety
328
9.
FUNCTIONAL SAFETY
Design requirements
Ref.1912
DDS
HARDWARE
· 318 ·
Example 2.
SS1 application that meets with Cat. 3, PL d - SIL 2
This safety function corresponds to a controlled stop in accordance with stop
category 1 of IEC 60204-1.
The safety function SS1 referred to in this examples corresponds to type "c)
safe stop 1 time controlled ·SS1-t·” as defined in IEC 61800-5-2.
It starts the motor deceleration and performs the STO function after a delay
time that has been previously specified for the application, but it does not
monitor that the deceleration is performed satisfactorily, and thus the SS1-t
has a residual risk. See
SS1-t in 9.6 Residual risks.
Considerations
The auxiliary +24 V DC power supply that powers the external safety
controller must be independent from the input power controlled by the
main external contactor - KM1.
In order to achieve PL d or SIL 2, the external safety controller must
check the feedback of the safety function as often as it is demanded.
F. H9/3
SS1-t safety function, Cat. 3, PL d - SIL 2.
KM1 auxiliary contact of - KM1 with EN 60947-5-1 approval
State definition: Drive Enable = O
Torque Off
Positive logic
EXTERNAL SAFETY
CONTROLLER
Cat.3 PL d, ISO 13849-1
A1
A2
11 12 21 22 67
S33 S34
58 68
AXD/SPD
PS/XPS/RPS
57
24 V
- F
- KM1
M
X2
X7
Drive Enable
AS1
AS2
KM1 ON
LINE/MAIN
13
14 24
Speed Enable

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fagor DDS Series and is the answer not in the manual?

Fagor DDS Series Specifications

General IconGeneral
BrandFagor
ModelDDS Series
CategoryDC Drives
LanguageEnglish

Related product manuals