LE-03MQ CT - User manual
17
5.2.5.2. Pulse rate
Setup value option kWh/kvarh per 1 pulse. Values: 0.01 / 0.1 / 110 / 100.
5.2.5.3. Pulse duration
Option of setting pulse length for output. Values: 200, 100 or 60 ms.
From the setup menu, use and
buttons to select the pulse rate option.
Press to enter the selection routine.
The current setting will flash.
Use Use andand buttons to select
value: 0,01 /0,1 /1 /10 /100 per pulse.
Press to confirm selection.
PressPress to return to the main set up menu.
From the setup menu, use and
buttons to select the pulse width option.
Press to enter the selection routine.
The current setting will flash.
Use and buttons to choose value:
200, 100 or 60 ms.
Press to confirm the selection.
PressPress to return to the main set up menu.