6
fantech
Installation examples (Cont'd)
Example only – duct configuration may differ depending on the model.
PARTIALLY DEDICATED SYSTEM (BETTER)
1. Stale air is drawn from key areas of the home (bathroom,
kitchen, laundry room).
2. Fresh air is distributed through habitable rooms in the house
(bedrooms, living room) via forced air system.
3. The ERV's airflow must be balanced on site using the procedure
found in section "AIRFLOW BALANCING"
ERV/Furnace ducting for Partially Dedicated System
Stale air coming from different areas of the
house (ie bathroom, kitchen).
* Unit air flow should be balanced while ERV is on "High" speed and fur-
nace blower is running.
Air return
1 m (3' 3")
min.
recommended
Cold air
return
* Ductwork layout may dif-
fer depending on model