EasyManua.ls Logo

Fantech SHR 2004 - Installation Examples (Continued); Simplified Installation - Option 2

Fantech SHR 2004
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM &
EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN & SUPPLY AIR SIDE
Simplified Installation
Option 2
(Supply/Return Method)
NOTES:
1. Furnace blower must operate when ventilation from HRV is required.
The furnace should be set to run continuously or interlocked with HRV.
2. The exhaust air connection should be upstream of the supply air con-
nection to prevent exhausting any fresh air.
3. Weatherhood arrangement is for illustrative purposes only. 3m (10')
minimum separation and 460mm (18") above grade is recommended.
4. Due to the differences in pressure between the HRV and the equip-
ment it is being connected to, the HRV‘s airflow must be balanced on
site, using the procedure found section "AIRFLOW BALANCING".
INSTALLATION EXAMPLES (CONT'D)
NOTE: In the case of a sim-
plified installation, Option 1
is recommended.
Stale air coming from different areas of the
house (ie bathroom, kitchen).
* Unit air flow should be balanced while HRV is on "High" speed and fur-
nace blower is running.
Outside
Air return
1 m (3' 3")
min.
recommended
Cold air
return
* Ductwork layout may dif-
fer depending on model
HRV/Furnace ducting for Simplified Installation - Option 2
Example diagram only - Duct configuration may change depending on model

Other manuals for Fantech SHR 2004

Related product manuals