EasyManua.ls Logo

FBD 373 - Page 42

FBD 373
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
37X INSTALLATION & OPERATION MANUAL
372/373 MODELS
40
10.2 Fault Codes
The dispenser records all errors, or faults, that occur. A history of these faults can be found in the FAULT CODE HISTORY
menu located in the SERVICE MENU. Each error has a three-digit number associated with it. The first two digits are the
error number and the third digit indicates the barrel number with the error. If the third digit is a 0 (zero) then the error is a
common error to all barrels or it is a dispenser error.
Error #011, 012, 013: Syrup Out
The syrup pressure is less than 45 PSI (310 kPa). For multi-flavor dispensers, this is the base syrup.
Error #020: CO Out
The CO pressure is less than 45 PSI (310 kPa).
Error #030: Water Out
The water pressure is less than 45 PSI (310 kPa).
Error #041, 042, 043: Tank PSI = 0
The tank pressure did not rise from 0 PSI (0 kPa) when filling.
1 Replace the empty BIB.
2 Ensure the gas line is connected to the BIB pump.
3 Ensure the BIB pump is operating correctly.
4 Ensure the gas tank is not empty.
5 Ensure the syrup shuto valve at the solution module is turned on.
6 Ensure any syrup shuto valves at the back of the dispenser are not turned o.
7
Ensure the syrup supply pressure at the dispenser is reading 70 PSI (483 kPa). Adjust the regulator
if needed.
8 Ensure the syrup pressure transducer is connected and working properly.
1 Replace or rell the CO tank.
2 Ensure the CO shuto valve at the back of the dispenser is not turned o.
3 Ensure the CO pressure transducer is connected and working properly.
4
Ensure the CO supply pressure at the dispenser is reading 70 PSI (483 kPa). Adjust the regulator
if needed.
1
Ensure the water line to the dispenser is on and that the water shuto at the solution module is
turned on.
2 Ensure the gas supply line is connected to the water pump and that the pump is not stalled.
3
Ensure the gas supply pressure at the dispenser is reading 70 PSI (483 kPa). Adjust the regulator if
needed.
4 Ensure the water pressure transducer is connected and working properly.
1 Run the ll diagnostic sequence to determine the reason for the failure.

Table of Contents

Related product manuals