Inputs
Select
View
# keys: enters loop & address (restriction: Address 200)
< >: Scrolls up or down to next available device.
OK: Accepts address, opens Configure Input Device Menu,
Configure Output Device Menu, Control Output Menu, or
Enable/Disable Device Menu, as appropriate.
1: Opens Set Input Type Menu.
2: Opens Assign Input To Group Menu.
3: Opens Set Verify/PAS Function Menu (sensors only).
4: Opens Set Sensitivity Menu (Ion, Photo devices only).
5: Opens Set SLC Device Location Menu.
6: Displays all settings for current device.
7: Copies all settings of the specified device (last input modified).
<>: scroll through types which match this physical device.
# keys: enter type number (no restrictions; see type table)
Shows type and associated Response.
BKSP/EDIT: If selected device type is editable, or if it is not edit-
able but there is room to create a new user- editable type, opens
Add Type menu (Menu 35). ^ indicates that editing is possible.
No restrictions on group assignment
Options are: Default, None, Smoke Verify (Ion/Photo only), PAS
1: Scrolls through Day Sensitivity options.
2: Scrolls through Night Sensitivity options.
Options vary by type, may include: Default, 1.00%, ... 2.00%
Shows: Loop and Address, Device Type, Location Lbel, Device
Response, and I/O Group. Shows Verify/PAS settings and day
sensitivity setting if applicable (if device is set for default
sensitivity, shows default day sensitivity). No changes can be
made.
[L,AAA] 1: Verification (Default)
[L,AAA] Ion Duct Det FLR2 Storeroom
Alarm Grp23 Vfy:Default 1.75%
[SELECT] Loop,Address: 1,001
[DEVICE] Key in or use <,>
[L,AAA] Group 007 (00=no group)
[GROUP] Key in Group# or use <,>
[L,AAA] Ion Duct Det 01 (Alarm)
[TYPE ] ^ Key in Input Type # or use <,>
[CONFIG] 1:Type 2:Group 3:Verify 4:Sens
[L,AAA ] 5:Location 6:View 7:Copy L,AAA
Main
Config
Inputs or Outputs
——————— or ——————-
Main
I/O
Control or Ena/Dis
Main
Config
Inputs
Select
Main
Config
Inputs
Select
Type
[L,AAA] 1:Day Sensitivity (Default)
[SENS ] 2:Night Sensitivity (Default)
Inputs
Select
Group
Inputs
Select
Verify
Inputs
Select
Sens