EasyManua.ls Logo

FCI 7100 SERIES - Page 34

FCI 7100 SERIES
47 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Select
General Response
1: Opens Set Output Type Menu.
2: Opens Assign Output To Group(s) Menu.
3,4: Unused.
5: Opens Set SLC Device Location Menu.
6: Displays all settings for this device.
7: Copies settings of the specified device (last output modified).
<>: scroll through types which match this physical device # keys:
enter type number (no restrictions: see type table)
Output device types cannot be edited.
If the new type is an input device, “OK” key returns to the System
Config menu, otherwise to Output Config.
1: toggles specified general group membership YES/NO.
<>: scrolls through list of general groups.
Number keys: set group number.
<>: select which of the three possible groups to set.
Shows: Loop and Address, Type, Location, General responses,
Group membership. General responses show above abbreviations
if the output is activated in that condition, or —- if not.
# keys: enters group number.
<>: Scrolls up or down to next group.
OK: Accepts group number, opens Configure Group Menu.
1: Toggles General Alarm response on/off (applies to alarms
initiated by Alarm, Manual, Waterflow, and Tornado devices, for
both Day and Night general alarm).
2: Toggles General Supervisory response on/off (applies to off-
normals initiated by Supervisory and Tamper devices).
If a group contains inputs of several types (an unusual case), the
appropriate general flag is applied for each new alarm/off-normal.
Other general groups (e.g. Trouble, Action) cannot be suppressed.
[L,AAA] Activates for Day Alarm (YES)
[GNL RSP] select condition 1:YES/NO
[L,AAA ] Group 1: 36 (00 = none)
[GROUPS] Key in group # <,> change
[L,1AA] Slncbl NAC Main Lobby
ALd ALn ACT SPV TOR WKT TBL 02 00 00
[SELECT] Group number: 03
[GROUP ] Key in group# or use <,>
[GROUP] Activates General Alarm (NO)
[ 03 ] Activates Genrl Supervisory (YES)
[CONFIG] 1:Type 2:General Resp 3:Groups
[L,AAA ] 5:Location 6:View 7:Copy L,AAA
[L,AAA] 34 Silenceable Signal AOM
Key in Output Type# or use <,>
Main
Config
Outputs
Select
Main
Config
Groups
Select
General
Response
Main
Config
Outputs
Select
Type
Select
I/O Group
Select
View
Main
Config
Groups
32 of 43 9000-0447
Technical Manuals Online! - http://www.tech-man.com

Table of Contents