12
SERVICING
31
FIREBIRD ‘S’ RANGE
NOTE: IT IS STRONGLY RECOMMENDED THAT SERVICING IS CARRIED OUT
BY A COMPETENTLY QUALIFIED ENGINEER.
RECOMMENDED SERVICE INTERVALS
C2 Kerosene Annually
Before carrying out a service it is recommended that the following
is checked:
A). Smoke
B). CO2
C). The flue gas temperature
D). Oil pressure
E). Ensure flue is unrestricted & operating properly
At the same time check for oil and combustion leaks. Advance to service
ONLY after ensuring that both electric and oil supply to boiler is safely isolated
THE OIL TANK
Draw off any accumulated water and sludge from the tank by opening the drain cock. Turn off the oil
supply and remove the filter bowl, then wash the element clean with kerosene. Steel Tank Only
THE BOILER
Remove combustion access door for access to baffles and to clean heat exchanger.
Check insulation sealing and its silver foil lining in combustion access door - replacing when necessary.
When refitting this door be careful not to damage the foil and insulation by over tightening.
THE BURNER
Check performance of oil-nozzle and replace as necessary.
Ensure correct specification replacement nozzle is used.
Check all oil filters and replace as necessary.
Remove burner and clean blast tube and ensure that airways are clear.
Ensure electrodes are clean, dry, not broken and are set as per burner specifications.
Clean fan and photocell.
Once again check flexible oil lines and connections for damage or leaks, replace as necessary.
Combustion Check
Carry out combustion analysis and ensure that boiler is performing to specification outlined in
manual. Flue conditions may cause deviation from these figures.
Always keep careful record of flue gas analysis results including any verbal and written advice to
customer (householder). Always check carefully for restricted or blocked flue. If possible record
CO levels and advise customer of need to keep boiler room well ventilated.
SERVICING RECORD - PAGE 42