EQUIPMENT: FIRECLASS Prescient III WRITTEN BY: RKP
PUBLICATION: OMFCPRES3IN CHECKED BY: AP
ISSUE No. & DATE: 0 02/02/12
PAGE 4 of 43
6) Repeater outputs for:
(i) Zone 1 Fire Detected
(ii) Zone 2 Fire Detected
(iii) Auxiliary Zone Fire Detected
(iv) Manual Release Activated
(v) Extinguishing System Disabled
(vi) Isolation Valve Closed
(vii) Isolation Valve Abnormal
(viii) Emergency Hold Activated (configurable for
auto & manual mode)
(ix) Emergency Abort Activated (configurable
for manual only mode)
7) Two Auxiliary 24VDC supply outputs.
8) RS485 communication link to drive external
Status Lamp Units.
9) Fully monitored inputs for:
(i) Gas Discharged Pressure Switch
(ii) Gas Low Pressure Switch
(iii) Gas Isolation Valve
(iv) Gas Trapped In Manifold
(v) Emergency Hold Switch
(vi) Emergency Abort Switch
(vii) Manual Only (Lock-Off) Switch
(viii) Remote Controls Switches (Sound alarms,
Silence Alarms, Reset)
10) Fully Monitored Outputs (Configurable for
Volt-Free operation) for:
(i) First Stage Shutdown
(ii) Second Stage Shutdown
(iii) Third Stage Shutdown
(iv) Auxiliary Fire Signal
(v) Auxiliary Fault Signal
(vi) Gas Released Signal
11) Volt-Free Relay Contacts for Auxiliary
Equipment Reset
12) Terminals for Internal Standby Batteries
13) Site Configuration DIL Switches
14) Fault indication LEDs
15) Internal Buzzer
Figure 1 – Enclosure Dimensions
FIRE STATUS
COMMON STATUS
USER CONTROLS EXTINGUISHING STATUS
FIRE
FIRE SIGNAL
ZONE 1
ZONE 2
AUX ZONE
REMOTE SOUND ALARMS
REMOTE CONTROLS FAULT
FIRE SOUNDER FAULT/DISABLED
POWER SUPPLY ON
GENERAL FAULT
POWER SUPPLY FAULT
SYSTEM FAULT
EARTH FAULT
FUSE FAILED
FAULT SIGNAL FAULT/DISABLED
SOUNDER TEST
AUTO & MANUAL
MANUAL ONLY
MANUAL RELEASE ACTIVE
SYSTEM ACTIVATED
GAS RELEASED
GAS RELEASED SIGNAL ACTIVE
EMERGENCY ABORT ACTIVE
EMERGENCY HOLD ACTIVE
CIRCUIT FAULT
GAS LOW
GAS TRAPPED IN MANIFOLD
ISOLATION VALVE ABNORMAL
ISOLATION VALVE CLOSED
MANUAL RELEASE FAULT/DISABLED
EXTINGUISHING DISABLED
GAS RELEASED SIGNAL DISABLED
SHUTDOWN OUTPUTS DISABLED
SECONDS
TO
DISCHARGE
SILENCE
ALARMS
FIRE
RESET
SILENCE
BUZZER
SELECT
ON/OFF
SCROLL
OFF
ACCESS
CONTROLS
ON
TEST
DISABLE
ENABLE
AUTO & MAN/
MANUAL ONLY
EXTINGUISHING
SYSTEM RESET
(INHIBITED)
RESOUND
ALARMS