EasyManua.ls Logo

FireClass Prescient III - 14 Construction Productsd; Irective; Onstruction P Roducts D Irective

Default Icon
43 pages
Print Icon
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EQUIPMENT: FIRECLASS Prescient III WRITTEN BY: RKP
PUBLICATION: OMFCPRES3IN CHECKED BY: AP
ISSUE No. & DATE: 0 02/02/12
PAGE 43 of 43
14. Construction Products Directive
0086
Control Equipment Ltd
Hillcrest Business Park
Cinder Bank
Dudley
West Midlands
DY2 9AP
United Kingdom.
08
0086-CPD-517159
EN54-2
Control and indicating equipment for fire detection and fire alarm systems for buildings
Provided options:
Outputs to fire alarm devices.
Output to fault warning routing equipment.
Test condition.
EN54-4
Power supply equipment for fire detection and fire alarm systems for buildings
EN 12094-1
Electrical automatic control and delay device
Environmental class A
1 flooding zone
CO
2
-high-pressure, CO
2
-low-pressure, inert gas, Halocarbon
Provided options:
Extinguishing system delay.
Reception of a signal representing the flow of extinguishing agent.
Monitoring of status of components:
Low pressure/low weight.
Reception of signal from an emergency hold device.
Separate monitoring of the status of non-electrical disable device[s].
Input from auto/manual selector switches.
Transmission of a triggering signal to equipment within the fire extinguishing system:
Optical warning devices.
Transmission of signals to equipment outside the fire extinguishing system.
Reception of signal from an emergency abort device.
Activation of alarm devices with different signals.
Response delay activated condition maximum 3s.
Response delay triggering of outputs maximum 1s.

Table of Contents

Other manuals for FireClass Prescient III

Related product manuals