ZONE CIRCUITS
+
-
+
-
+
-
+
-
1 2 AUX
MR
GAS
REL.
GAS
LOW
ISO.
VALVE
GAS
TRAPPED
Z1 Z2 AUX MR 1 2 3 4 5
OUTPUTS
HOLD ABORT
REMOTE
CTRLS
AUTO/
MANUAL
Repeat Output – Isolation Valve Abnormal
Repeat Output – Isolation Valve Closed
Repeat Output – Actuators Disabled
Repeat Output – Emergency Abort Activated
(Panel in Manual – DIL SW Selectable)
Repeat Output – Emergency Hold Activated
(Panel in Auto – DIL SW Selectable)
Repeat Output – Manual Release Activated
Repeat Output – Auxiliary Zone Fire
Repeat Output – Zone 2 Fire
Repeat Output – Zone 1 Fire
Status Input – Gas Trapped in Manifold
10K EOL, 680R Activation
Status Input – Isolation Valve Status
10K Abnormal, 2K2 = Open, 680R = Closed
Status Input – Gas Low
10K EOL, 680R = Gas Low
(DIL SW configurable for Normally closed
operation)
Status Input – Gas Released Pressure Switch
10K EOL, 680R = Activated
Manual Release Input
21VDC, 10K EOL, 680R = Activated
(DIL SW configurable for 3K9 EOL)
Auziliary Zone Input
21VDC, 22uF EOL, 680R = Activated
Detectors & Call-points allowed
(DIL SW configurable for 3K9 EOL)
Detector Zone 2 Input – Protected Area Zone
21VDC, 22uF EOL, 680R = Activated
Fire Detectors only
(DIL SW configurable for 3K9 EOL)
Detector Zone 1 Input – Protected Area Zone
21VDC, 22uF EOL, 680R = Activated
Fire Detectors only
(DIL SW configurable for 3K9 EOL)
Input – Emergency Hold Switch
10K EOL, 680R = Activated
Input – Emergency Hold Switch
10K EOL, 680R = Activated
Input
Auto/Manual Mode Select Switch
10K EOL, 4K7 = Manual Only Mode
Remote Control Input
10K EOL, 4K7 = Sound Alarms
1K8 = Silence Alarms
560R = Reset System