EQUIPMENT: FIRECLASS Prescient III WRITTEN BY: RKP
PUBLICATION: OMFCPRES3IN CHECKED BY: AP
ISSUE No. & DATE: 0 02/02/12
PAGE 42 of 43
13. Mechanical, Electrical & Environmental Specification
Weight excluding batteries:
Mains Input Specification
Protection:
[Warning: Replace only with identical type & rating
of BEAB or VDE approved fuse]
T5AH250V
(20mm fuse, 5A, HBC, Anti-surge, approved to BS EN
60127 or equivalent.)
Minimum of 1mm
2
copper protected by a 5A fuse.
Panel Integrated Power Supply Output Specification
Maximum Short Term Current Output (I max b)
Maximum Continuous Current (I max a)
Minimum Output Current I(min)
26.5 - 28.6V (27.15V nominal)
Maximum Current Output, Mains Failed
Voltage Output, Mains Failed
Max Ripple including switching spikes
[full load, battery disconnected]
Output voltage adjustment
Electronic current limiting
Mains failed fault output:
Battery charger output:
Temperature compensated float charger
28.25V 0.1V@-5C
26.78 V0.1V@ +50 C.
Maximum internal resistance of battery & charger
circuit (Ri max)
Battery type:
POWERSONIC
[Warning: Replace only with identical battery]
L = 151
W = 98
H = 94
HT = 100
Battery circuit protection:
[Warning: Replace only with identical type & rating
of fuse]
F6.15AL250V 20mm fast blow glass fuse
Mains failed fault battery current:
60mA + Ancillary equipment current
Mains failed alarm battery current:
160mA
+ 20mA to 50mA for each zone in alarm
+ Ancillary equipment current
+ Alarm circuit current
+ Solenoid circuit current
Environmental Specification