EQUIPMENT: FIRECLASS Prescient III WRITTEN BY: RKP
PUBLICATION: OMFCPRES3IN CHECKED BY: AP
ISSUE No. & DATE: 0 02/02/12
PAGE 41 of 43
12.5 Remote Outputs & SLU Communication Connection Diagram
Panel Terminals
Z1 Z2 AUX MR 1 2 3 4 5
OUTPUTS
24V 0V
AUX
250mA
A B
S.L.U.
24V 0V
AUX
1A
+24V IN
+0V IN
+24V OUT
+0V OUT
RS485 A IN
RS485 B IN
RS485 A OUT
RS485 B OUT
Earth Bar
inside
Panel
Enclosure
Cable Shield
Connected to
Panel Earth Bar &
SLU Termination
Board
Connections to SLU
Repeat Output Isolation Valve Abnormal
Repeat Output Isolation Valve Closed
Repeat Output Actuators Disabled
Repeat Output Emergency Abort Activated
(DIL SW Selectable to Panel in Manual)
Repeat Output Emergency Hold Activated
(DIL SW Selectable to Panel in Auto)
Repeat Output Manual Release Activated
Repeat Output Auxiliary Zone Fire
Repeat Output Zone 2 Fire
Repeat Output Zone 1 Fire
Current
Limiting
Resistors,
Minimum
470R
Remote
Indicators,
Maximum
Current
50mA
RS485 SCREEN IN
RS485 SCREEN OUT
12.6 Glossary
1st Stage: (Pre-activated) Fire condition on zone 1 or zone 2 in system Automatic with panel configured to
double knock mode.
2nd Stage: (Activated) Pre-discharge time delay running.
3rd Stage: (Activated) Pre discharge timer ended, actuators activated.
Discharged: (Released) Release of gas confirmed by signal from discharge pressure switch, or (when panel
configured to “No discharge pressure switch” mode) actuator activated.