11
Choose the desired units of measurement for pressure reading and verify that it matches with the calibrated pressure gauge
installed on the sensing line. Set the Cut-In value according to your system specifications. Cut-Out value will default to Cut-
In plus 10 PSI. To manually enter the cut-out, select the check-box besides it and enter the desired value (optional).
When finished, press the
Service Done
button. Any errors will be highlighted in red and, if forced, be logged in the
controller’s event logs.
The “First Start up” is now completed. The controller is fully installed and configured.