EasyManua.ls Logo

Flowserve 6LR-18A - Page 39

Flowserve 6LR-18A
116 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Model Number: 5KS445SAA2067 / Version: v17012876.01 Friday, January 06, 2017
Visit us: www.gemotors.com
Page 5 of 10
Performance Characteristics
1st Winding 1st Connection
Design: 44BD1087AA
Marks:
PROJECT# 1244763-1 CARTER & VERPLANCK
LOAD % 125.0 115.0 100.0 75.0 50.0 25.0 0.0
% EFF
95.51 95.67 95.80 95.95 95.51 93.11 0.00
% PF
88.78 88.70 88.00 85.88 79.30 59.59 4.72
AMPS
206.97 190.27 167.00 127.78 92.68 63.26 48.12
TORQ(FL)#FT
439.97
TORQ(LR)%FL
119.02
TORQ(BD)%FL
251.57
AMPS(LR)
1001.31
PF AT START
0.25
This motor is capable of two cold or one hot start with a maximum connected load inertia of 4849.0 Lb-Ft Sq (204.3 Kg-
meter Sq) at 100% voltage, where the load torque varies with the square of the speed. Acceleration time with maximum
inertia and the above load type is 77 seconds. Safe stall time at 100% voltage is 151 seconds cold, 100 seconds hot.
Rotor inertia is 78.73 Lb-Ft Sq (3.318 Kg-meter Sq).
Open Circuit A-C:
1.617
Short Circuit D-C:
0.030
Short Circuit A-C:
0.072
X/R Ratio:
11.410
Stator Slots:
72
Rotor Slots:
58

Table of Contents

Related product manuals