Page #8 background imageLoading...
Page #8 background image
Pump Division
Flowserve Pumps
Flowserve Corporation
Pump Division
www.flowserve.com
3900 Cook Boulevard
Chesapeake, Virginia
23323-1626
Telephone 757-485-8000
Facsimile 757
-485-8191
January 27, 2017
Comments & Clarifications
---------------------------------
Specification Section: 11216 – Horizontal Split Case Centrifugal Pumps
16150 – Electric Motor
Section 01010- Summary of Work
Addendum 1 & 2
Customer: Carter & Verplanck Tag: LARGE HIGH SERVICE 1&2
Project: West Nassau Regional WTP Order No.: 047-1244763
Service: Finished Water S/N: 1244763CHP001A/B
P.O No.: 18227 Rev.: 0
I. CLARIFICATIONS
A. Flowserve can only guarantee one set of (rated) condition, as noted in advertised
and submitted standard performance curve, 2,000 USgpm @ 200 ft TDH, 1750
rpm, with efficiency of 79%.
B. Factory performance testing, HI 14.6 Grade 1U, shall be witnessed by
Flowserve registered professional Engineer and test curves shall be submitted
for approval prior to shipping. Calibrated shop motor shall be used during
factory testing.
C. Pump delivery is 18 weeks upon receipt of formal release to fabrication.
D. Start-up, Commissioning, and Training are not part of Flowserve scope of work,
and shall be provided by an authorized representative.
II. EXCLUSIONS
A. Off-loading at jobsite, any labor or tools for Assembly or Installation, Field
operation, Field performance testing including Field vibration or noise testing
instruments or analysis
B. Suction or Discharge piping, mechanical couplings, supports, tie rods, leveling
screws, fittings, etc.
C. Air relief valves / Vacuum valves / Isolation valves, etc.
D. Vibration isolation equipment
E. Seal water or drain accessories such as piping, flow indicators, pressure
reducing valves, Y strainers, fittings or tubing
F. Gauges, T cocks, anchor bolts, templates or accessories
G. VFDs or any type of Controls, Instrumentation, MCCs, Starters, Power Factor
Correction Capacitors, Panels, cable, wiring, conduits, temperature or

Table of Contents