6. To stop the calibration process, depress the push button for approximately 3
seconds until the green LED flashes.
7. At the end of calibration, the sensor changes to the condition-monitoring mode. The
calibrated reference values are also saved even if the power supply is
disconnected.
These calibrated values can now be compared with actual readings. Importantly,
the maximum value, which has been measured during the calibration phase, is
saved.
Condition monitoring mode is now activated.
Picture: Push button sensor
Caution! Explosion hazardous area
Ensure that the screwdriver cannot make contact with other parts of the
device other than the terminals.
Ensure that the device is kept free from moisture and foreign bodies.