Earth Ground Tester
Specifications
17
Measuring
Range
Resolution Display
Range
Intrinsic
Uncertainty
Operating
Uncertainty
IEC 61557*
0.15 to 20 Ω 0.01 Ω 0 to 19.99 Ω
200 Ω 0.1 Ω 20 to 199.9 Ω
2 kΩ 1 Ω 200 to 1999 Ω
± (6 % of
measured
value + 5D)
± (18 % of
measured value
+ 5D)
*Covers all deviations caused by influence quantities E
1
-E
5
If the deviation E4 caused by high probe or auxiliary probe resistance is
higher than specified W flashes. Measured values are outside of the
specified operating uncertainty.
Measuring time: 8 seconds (average from when START is pressed)
Limit input: Tester retains set value even if instrument is turned
off (assuming battery power supply is sufficient)
If Tester detects stray interference voltage 20 V, W is displayed and the
measurement is not started.