Earth/Ground Tester
Operation
13
R
A
4-Pole Measurements
To make 4-pole measurements:
1. Select 4 POLE function. See Figure 5.
2. Connect test leads.
Connect terminals E/C1 and ES/P1 to the earth system to be measured with the
two supplied test leads (1.5 m). Place two ground stakes in earth/dirt. Minimum
distance between earth electrode (E/C1), probe (S/P2), and auxiliary earth (H/C2)
should be at least 20 m. The ES test lead eliminates the influence of the test
leads.
Connect the stakes with the 25 m and 50 m cable reels to H/C2 and S/P2 as
shown below.
3. Push START.
indicates that a measurement is in progress. For a continuous
measurement, continue to push the START button.
4. indicates a completed measurement. The result is kept on the display until a
new measurement is started or the rotary switch is turned.

Other manuals for Fluke 1623-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fluke 1623-2 and is the answer not in the manual?

Fluke 1623-2 Specifications

General IconGeneral
USB portYes
Control typeButtons, Rotary
CertificationIEC61326-1, CE
Housing colorBlack, Yellow
Display digits1999 digits
Measuring time6 s
Maximum voltage48 V
Display technologyLCD
Number of memory records1500
Storage temperature (T-T)-30 - 60 °C
Operating temperature (T-T)-10 - 50 °C
International Protection (IP) codeIP56
Battery sizeAA
Battery voltage1.5 V
Battery technologyAlkaline
Battery life (measurements)3000
Number of batteries supported6
Weight and Dimensions IconWeight and Dimensions
Depth187 mm
Width250 mm
Height133 mm
Weight1100 g