EasyManua.ls Logo

Fluke 8845A - Page 28

Fluke 8845A
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8845A/8846A
Programmers Manual
20
In the following examples, <space> between commands is for readability only. However a
<space> between a command and its argument is required. The PRINT command sends a
terminator at the end of the string.
The following string configures the Meter and triggers an ohms reading to be shown
on the primary display when the Meter is in Fluke 45 emulation mode.
EXAMPLE 2:
The following string configures the Meter and triggers an ohms reading to be shown
on the primary display when the Meter is in 8845 or 8846 emulation mode.
EXAMPLE 1:
PRINT @3, "*RST;
IEEE-488 bus address
Reset to power-up configuration
Select 300 range
Select function
Select external trigger
(Rear panel trigger disabled, no trigger delay)
Trigger a reading
Return reading shown on primary display
Select medium reading rate
PRINT @3, "*RST; CONF:RES 1; :RES:NPLC 1; :TRIG:SOUR BUS; :INIT; *TRG; FETCH?"
IEEE-488 bus address
Reset to power-up configuration
Select 1 PLC measurement rate
Select function 1 ohm range
Wart-for-trigger state
Trigger a reading
Return reading shown on primary display
Select Bus triggering
OHMS; RANGE 1; RATE M; TRIGGER 2; *TRG; VAL1?"
aam19f.eps
Figure 2. Typical IEEE 488 Input String

Table of Contents

Other manuals for Fluke 8845A

Related product manuals