16 REF4P, REF5P and REF5BBP-T Undercounter Refrigerators
Alarm Codes
When the unit senses an alarm, the display will ash the following codes.
Value Description
HA1 Temperature is above the High Alarm#1 set point.
LA1 Temperature is below the low Alarm #1 set point.
HA2 Temperature is above the High Alarm #2 set point.
LA2 Temperature is below the Low Alarm #2 set point.
SFS Suction line temperature probe fell below the suction failsafe temp of -15 C (5 F).
DFA Defrost time out (lasted the full 30 minutes)
DFS Discharge line temperature probe rose above the discharge failsafe temp of 121 C (250 F).
Lob Low battery alarm.
dA Door open alarm.
Error Codes
Value Description
P1-P8 Controller is not sensing the probe.
F9 Error saving new parameter values to permanent storage.
F10 Incomplete model conguration.
F11 Number/membrane is sticking.
F21 Key shorted on user interface.
F22 Communication error with user interface.
F23 Communication error with Machine Control.
Advanced Settings
The refrigerator can be further customized through the rst level (L1) and second level parameters (L2) in the
chart below.
1. Press and hold SET and UP arrows simultaneously until L1 is displayed.
2. Use the UP and DOWN arrows to navigate the parameters. When the desired parameter is displayed,
press SET.
3. Use the UP and DOWN arrows to navigate the sub menu of the parameter. Press SET to accept and
the display will return to the parameter list (after 30 seconds the display will return to the temperature
display).
Parameter Display Description
Beeper Function bPr Controls the audible beeper function on the controller. Off, All, door, Alarm,
Error.
Beeper Volume bPu Sets the volume of the beeper: 0 (minimum) to 10 (maximum).
Button Clicks btc Sets if a beep should sound each time a button is pressed. Yes or No.
Sleep Function SLP Determines if sleep function activated from the panel. Yes or No.
Sleep Timer SLt Amount of time before the screen blanks automatically. 0 s to 600 s.
Alarm1 High Temp A1H High temperature to activate alarm1. User set point to 121 C (250 F).
Alarm1 Low Temp A1L Low temperature to activate alarm1. User set point to –46 C (–50 F).
Alarm1 Probe A1P Probe for Alarm. P1 (cabinet air), P2 (evaporator), P3 (simulation bottle), P4 (not
used), P5 (not used), P6 (evaporator line), P7 (discharge line), P8 (not used).
Units unt Display temperatures in degrees C or F. F or C.