28 REF4P, REF5P and REF5BBP-T Undercounter Refrigerators
Parameter Default Value Range Description
Power Alarm
Relay
No Yes, No Denes if relay should open/close on power alarm.
Power Alarm
Timer
5 minutes 0 - 120 minutes Delay before sounding the power alarm.
Battery Level Battery Level
Data Storage Yes Yes, No Overwrite circular data?
Data Full Alarm No Yes, No Alarm when data memory is full?
Data log
Sample Rate 5 minutes 0 - 360 minutes minutes between data sampling. 0=Off
Data Duration
Data Storage Yes Yes, No Overwrite circular data?
Data Full Alarm No Yes, No Alarm when data memory is full?
Track Events Yes Yes, No Track events with log
P1 Datalog Yes Yes, No Log P1 to event log
P2 Datalog No Yes, No Log P2 to event log
P3 Datalog Yes Yes, No Log P3 to event log
P6 Datalog No Yes, No Log P6 to event log
P7 Datalog No Yes, No Log P7 to event log
Defrost
Manual Defrost No Yes, No Force the unit into a defrost
Defrost Control Power on "Power on,manual
only,disable,time of day,
compressor on time"
Denes tactic for initiating a defrost
Defrost Type Evaporator Heater, Evaporator Type of defrost (forced heat or fan only)
Defrost
Termination
Tactic
Temperature time, temperature Defrost end routine
Defrost Timer 8 hours 0-720 hours Hours between defrost cycles
Defrost
Termination Temp
4 C (38 F) 0 to 66 C (32 to 150 F) When set to temperature, denes temp.
Defrost Duration
(mins)
30 minutes 0-60 minutes When dtr set to t(time), duration of defrost. Failsafe
time when set to temp.
Evap Fan Defrost
Delay
30 seconds 0-300 seconds Time to delay starting of evap fan after restarting
system. (ignored if dtp=Fan)
Drip Timer 0 seconds 0-300 seconds delay at end of defrost cycle before starting system.
Evap Fan Restart Temperature Time , Temperature Denes if the evap fan should restart on time or
temp after compressor starts during the defrost
routine. T=time, Tp=temp
Evap Fan Temp 9 C (15 F) 37 to 13 C (–35 to 55 F) Temperature to restart evap fan, when EFr= temp.
Graphing
X Axis Range
(hrs)
168 hours 1-384 hours Time span for x-axis
Y Axis Minimum 1 C (30 F) 46 to 121 C (–50 to 250 F) Minimum temperature shown on graph
Y Axis Maximum 27 C (80 F) 46 to 121 C (50 to 250 F) Maximum temperature shown on graph
Graph Show
Alerts
No Yes, No Determines whether alerts are displayed on the
graph
P1 Graph Display NO Yes, No Determines whether to graph probe 1
P2 Graph Display No Yes, No Determines whether to graph probe 2
P3 Graph Display Yes Yes, No Determines whether to graph probe 3