1
Please check grid-connection, e.g. wires, interface etc.
2
Checking grid usability.
3
Or seek for help from us.
1
Check the panel’s open-circuit voltage whether the value is
similar or already >550Vdc.
2
Please seek help from us when voltage ≤550Vdc.
1
Disconnect PV (+), PV (-) with DC.
2
After the LCD switches off, reconnect and check again.
3
Please seek for help from us if it cannot go back to normal state.
1
Check if the environment temperature is over the limit.
2
Or seek for help from us.
1
Wait for one minute after the inverter reconnect to grid.
2
Disconnect PV (+), PV (-) with DC.
3
After the LCD switches off, reconnect and check again.
4
Please seek for help from us if it does not go back to normal state.
1
Disconnect PV (+), PV (-) with DC.
2
After the LCD switches off, reconnect and check again
3
Please seek for help from us if it does not go back to normal state.
1
Check the impedance among PV (+), PV (-) and ground.
Impedance should be >1Mohm.
2
Please seek for help from us if it cannot be detected or the
impedance is <1Mohm.
1
Disconnect PV (+), PV (-) with DC.
2
After the LCD switches off, reconnect and check again.
3
Please seek for help from us if it does not go back to normal state.
1
Disconnect DC and AC connector, check the surrounding equipment
on the AC side.
2
Reconnect the input connector and check the state of inverter after
troubleshooting.
3
Please seek for help from us if it does not go back to normal state.
1
Disconnect PV (+), PV (-) with DC.
2
After the LCD switches off, reconnect and check again.
3
Please seek for help from us if it does not go back to normal state.