FP4000 Rev0204
8
INSTALLATION
The FP4000 display module, flow sensor, and pressure transducer are compatible
for use with any size piping.
Note: Plumbing systems are always unique and may cause small deviations
in the factory calibration. It is recommended that the calibration procedure
be performed after installation.
Install Display Module
The pressure gauge/flowmeter display modules are interchangeable. It is
recommended that the calibration be checked if modules are swapped.
Note: It is recommended to have the primary pressure gauge/flowmeter
mounted close to the associated discharge valve.
1. Measure and mark mounting location for display module panel cutout and
mounting screw holes. Make sure there is clearance behind the panel for the
display and cables before cutting holes. Refer to Figure 2 for layout and
dimensions.
2. Cut out a 3.75-inch diameter hole and drill two holes (clearance or tapped) for
10-32 mounting screws.
3. Place display module in position and secure with two screws.
4. Connect the display module cables and wires. (Refer to Wiring section.)