12 PB
Vert-I-Pak is designed to install through an exterior wall with a plenum (VPAWP1-8, VPAWP1-14) and an external louver. If the default
plenum and louver combinations are not used, the selections and design must be evaluated by us to ensure the total pressure drop does not
exceed the maximum allowable limits.
Condenser External Pressure
Model Design Maximum
CFM ESP (“WP) ESP (“WP)
VHA09 650 0.03 0,12
VHA12 650 0.03 0,12
VHA18 950 0.03 0,12
VHA24 950 0.03 0,12
Table 106 (Airow Data)
SPECIFICATIONS
Airow Data (Condenser)