FRIGOMAT G5 G10 M04.37562 R.2021.10.23 15
P Description Min Max Step G5 G10 Note
P1 Model selection 1 2 1 2 2 -
P2 Probe alignment CYLINDER -20,0°C +10,0°C 0,1°C 0,0°C 0,0°C -
P3 Probe alignment SUCTION -20,0°C +10,0°C 0,1°C -10,0°C -10,0°C -
P4 Forzed freezing 0” 250” 1” 25” 25” -
P5 Probe temperature CYLINDER pr.1 +10,0°C -30,0°C 0,1°C -3,0°C -3,0°C -
P6 Probe temperature SUCTION pr.1 +10,0°C -50,0°C 0,1°C +2.0°C +2.0°C -
P7 Probe temperature CYLINDER pr.2 +10,0°C -30,0°C 0,1°C -4,0°C -4,0°C -
P8 Probe temperature SUCTION pr.2 +10,0°C -50,0°C 0,1°C +2.0°C +2.0°C -
P9 Probe temperature CYLINDER pr.3 +10,0°C -30,0°C 0,1°C -11,5° -11,5° -
P10 Probe temperature SUCTION pr.3 +10,0°C -50,0°C 0,1°C 0,0°C 0,0°C -
P11 Probe temperature CYLINDER pr.4 +10,0°C -30,0°C 0,1°C -12,0°C -12,0°C -
P12 Probe temperature SUCTION pr.4 +10,0°C -50,0°C 0,1°C 0,0°C 0,0°C -
P13 Probe temperature CYLINDER pr.5 +10,0°C -30,0°C 0,1°C -12,5°C -12,5°C -
P14 Probe temperature SUCTION pr.5 +10,0°C -50,0°C 0,1°C 0,0°C 0,0°C -
P15 Probe temperature CYLINDER pr.6 +10,0°C -30,0°C 0,1°C -13,0°C -13,0°C -
P16 Probe temperature SUCTION pr.6 +10,0°C -50,0°C 0,1°C 0,0°C 0,0°C -
P17 Probe temperature CYLINDER pr.7 +10,0°C -30,0°C 0,1°C -14,0°C -14,0°C -
P18 Probe temperature SUCTION pr.7 +10,0°C -50,0°C 0,1°C 0,0°C 0,0°C -
P19 Forzed pause time after freezing 0’ 15’ 1’ 5’ 5’ -
P20 Time ON cyclic agitation 0” 120” 1” 0” 0” -
P21 ΔT CYLINDER probe for restart compressor in preservation 0,0°C +20,0°C 0,1°C 5,0°C 5,0°C -
P22 Growth failure alarm (Time-out) 0 2 1 2 2 0= Off, 1= 1 h, 2= 2 h
P23 Temperature orobe safety limit SUCTION -10,0°C -50,0°C 0,2°C -44,0°C -44,0°C -
P24 - - - - - - -
P25 Extra agitation time 0” 120” 1” 5” 5” -
P26 CYLINDER probe temperature to restart the compressor in night mode +10,0°C -30,0°C 0,1°C +4,5°C +4,5°C -
P27 SUCTION temperature probe to stop the compressor in night mode +10,0°C -30,0°C 0,1°C 0,0°C 0,0°C -
P28 Filter display 0°C 10°C 1°C 0°C 0°C -
P29 Display °C/°F 0 1 1 1 1 1 = °C, 0 = °F
P30 Restart time freezing limit OFF 60’ 1’ 35’ 35’ -
P31 ΔT probe safety CYLINDER to stop compressor in preservation 0,0°C +10,0°C 0,1°C +2.0°C +2.0°C -
P32 Delay starting compressor 0 10” 1” 0” 0” -
P33 Mixing after CN 0 20’ 1’ 0’ 0’ -
P34 WiMANAGER Functions - - - - - -
P35 Blackout alarms / T° > 5°C - - - - - -
P36 Card n. - - - - - -
P37 Total number of cards - - - - - -
- - - - - - - -
TAB V/01 : Programming chart