EasyManua.ls Logo

Fronius 3.0-3-S - Page 60

Fronius 3.0-3-S
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
60
Fronius Eco 25.0-3-S 27.0-3-S
Input data
MPP voltage range 580 - 850 V DC 580 - 850 V DC
Max. input voltage
(at 1,000 W/m² / -10 °C in an open circuit)
1000 V DC
Min. input voltage 580 V DC
Max. input current 44.2 A 47.7 A
Max. short circuit current of the solar modules
(I
SC PV
)
71.6 A
Max. feedback current
4)
48 A (RMS)
5)
Initial input voltage 650 V DC
Output data
Nominal output power (P
nom
) 25,000 W 27,000 W
Max. output power 25,000 W 27,000 W
Nominal grid voltage 3~ NPE 400 / 230 V or 3~ NPE 380 / 220
Min. grid voltage 150 V / 260 V
Max. grid voltage 275 V / 477 V
Nominal output current at 220 / 230 V 37.9 / 36.2 A 40.9 / 39.1 A
Max. output current 42 A
Nominal frequency 50 / 60 Hz
1)
Total harmonic distortion < 2%
cos phi power factor 0 - 1 ind./cap.
2)
Max. output fault current per period 46 A / 156.7 ms
General data
Maximum efficiency 98%
European efficiency U
DCmin
/ U
DCnom
/ U
DCmax
97.99 / 97.47 / 97.07% 97.98 / 97.59 / 97.19%
Overnight self-consumption 0.61 W & 357 VA
Cooling Controlled forced-air ventilation
Degree of protection IP 66
Dimensions h x w x d 725 x 510 x 225 mm
Weight (light version) 35.69 kg (35.44 kg)
Permissible ambient temperature - 25 °C - +60 °C
Permitted humidity 0 - 100%
EMC device class B
Overvoltage category DC / AC 2 / 3
Pollution level 2
Noise emission 72.5 dB(A) (ref. 1 pW)
Power-up current pulse
6)
and duration 65.7 A / 448 μs
Protection devices
Max. overcurrent protection 80 A
DC insulation measurement Integrated
Response to DC overload Operating point shift, power limitation
DC disconnector Integrated
DC overvoltage protection Integrated
RCMU Integrated

Table of Contents