Fronius Galvo 1.5-1 - Relay; Energy-Manager(In Relay Menu Item)

Fronius Galvo 1.5-1
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
EN
Relay Activate relay, relay settings, relay test
* these are only shown if the 'E-Manager' function has been activated under 'Relay mode'.
Relay mode
for selecting the different functions of the floating switch contact in the data communication
area:
- Alarm function
- Active output
- Energy-Manager
Relay test
Function test to determine whether the floating switch contact switches
Switch-on point (only if 'Energy-Manager' function is activated)
for setting the effective power limit beyond which the floating switch contact is switched on
Switch-off point (only if 'Energy-Manager' function is activated)
for setting the effective power limit beyond which the floating switch contact is switched off
Energy-Manager
(in Relay menu
item)
The 'Energy-Manager' function can be used to activate the floating switch contact in such
a way that it functions as an actuator.
Thus a consumer that is connected to the floating switch contact can be controlled by spec-
ifying a switch-on or switch-off point that depends on the feed-in power.
Setting range Relay mode / Relay test / Switch-on point* / Switch-off point*
Setting range ALL / Permanent / OFF / ON / E-Manager
Factory setting ALL
Alarm function:
Permanent /
ALL:
Switch the floating switch contact for permanent and temporary ser-
vice codes (e.g. brief interruption to energy being fed into the grid, a
service code occurs a certain number of times a day - can be adjusted
in 'BASIC' menu)
Active output:
ON: The floating NO contact is on all the time the inverter is in operation
(as long as the display is not dark and is displaying something).
OFF: The floating NO contact is off.
Energy-Manager:
E-Manager: Further details on the 'Energy-Manager' function may be found in the
"Energy-Manager" section.
Factory setting 1000 W
Setting range Switch-off point - max. nominal output of inverter / W / kW
Factory setting 500
Setting range 0 - Switch-on point / W / kW