36
Version Displays the version and serial numbers of the PC boards in the inverter (e.g. for service
purposes)
AC voltage derating: Status
ON / OFF voltage-dependent power reduction
GVDPRe
Threshold from which the voltage-dependent power reduction
begins
GVDPRv
Reduction gradient used to reduce the power, e.g.: 10% per volt
above the GVDPRe threshold.
Message
Activates the dispatch of an info message via Fronius Solar Net
Fault Ride Through: Status - default setting: OFF
If the function is activated, the inverter does not switch off im-
mediately in the event of a short-term AC voltage interruption
(outside of the limits specified by the grid supplier), but instead
continues to feed in power for a defined period.
DB min - default setting: 90%
"Dead Band Minimum" setting in percent
DB max - default setting: 120%
"Dead Band Maximum" setting in percent
k-Fac. - default setting: 0
Display area Display / Display Software / Integrity Checksum / Memory Card
/ Memory Card #1 / Power Stage / Power Stage Software / EMI
Filter / Power Stage #3 / Power Stage #4