EasyManua.ls Logo

Fronius Primo 10.0-1 208-240 - Page 27

Fronius Primo 10.0-1 208-240
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27
AC = Copper Wires (Cu)
Field Wiring with the following wire & wire combinations possible
Select appropriate cable cross-sections according to the actual device output! Do not combine copper and alu-
minum cables together in a single terminal.
AWG
solid
AWG
stran-
ded
3)
AWG
stranded
3)
/ solid
AWG
solid / solid
AWG
stranded
3)
/ stranded
3)
2
1)
2
1)
2/10 2/12 2/14 - 2/6
2)
2/10 2/12 2/14
4
1)
4
1)
4/10 4/12 4/14 - 4/6
2)
4/4
2)
4/10 4/12 4/14
6
1)
6
1)
6/10 6/12 6/14 6/10
2)
6/6
2)
4/8
2)
6/10 6/12 6/14
8
1)
8
1)
8/10 8/12 8/14 8/10
2)
8/6
2)
- 8/10 8/12 8/14
10
1)
10
1)
10/10 10/12 10/14 10/10
1)
10/6
2)
- 10/10 10/12 10/14
- - 12/10 12/12 12/14 12/10
2)
- - 12/10 12/12 12/14
AC = Aluminum Wires (Al)
Field Wiring with the following wire & wire combinations possible
Select appropriate cable cross-sections according to the actual device output! Do not combine copper and alu-
minum cables together in a single terminal.
AWG
solid
AWG
stran-
ded
3)
AWG
stranded
3)
/ solid
AWG
solid / solid
AWG
stranded
3)
/ stranded
3)
2
2)
2
1)
2/10
2)
2/12
2)
2/14
2)
- 2/6
2)
2/10
2)
2/12
2)
2/14
2)
4
2)
4
1)
4/10
2)
4/12
2)
4/14
2)
- 4/6
2)
4/4
2)
4/10
2)
4/12
2)
4/14
2)
6
2)
6
1)
6/10
2)
6/12
2)
6/14
2)
6/10
2)
6/6
2)
4/8
2)
6/10
2)
6/12
2)
6/14
2)
8
2)
8
2)
8/10
2)
8/12
2)
8/14
2)
8/10
2)
8/6
2)
- 8/10
2)
8/12
2)
8/14
2)
10
2)
10
2)
10/10
2)
10/12
2)
10/14
2)
10/10
2)
10/6
2)
- 10/10
2)
10/12
2)
10/14
2)
- - 12/10
2)
12/12
2)
12/14
2)
12/10
2)
- - 12/10
2)
12/12
2)
12/14
2)
1)
tested and proofed according UL
2)
not proofed according UL, connection to the terminal is possible
3)
all stranded wires < AWG 8 use & connect only with ferrules
DC = Copper Wires (Cu)
Field Wiring with the following wire & wire combinations possible
Select appropriate cable cross-sections according to the actual device output! Do not combine copper and alu-
minum cables together in a single terminal.
AWG
solid
AWG
stran-
ded
AWG
stranded / solid
AWG
solid / solid
AWG
stranded / stranded
4
2)
-----------
6
2)
6/6
4)
--------6/12
2)
6/14
2)
6/16
3)
8
2)
8
1)
8/10
1)
8/12
1)
8/14
1)
- 8/12
2)
- - 8/102) 8/12
1)
8/14
1)
8/16
3)
10
1)
10
1)
- - - 10/10
1)
10/12
1)
10/14
1)
- 10/10
1)
10/12
1)
10/14
1)
10/16
3)
12
1)
12
1)
- - - 12/10
1)
12/12
1)
12/14
1)
12/16
1)
12/10
1)
12/12
1)
12/14
1)
12/16
1)
14
2)
14
1)
- - - 14/10
1)
14/12
1)
14/14
1)
14/16
1)
14/10
1)
14/12
1)
14/14
1)
14/16
1)
16
3)
16
3)
-----16/14
1)
16/16
1)
16/10
3)
16/12
1)
16/14
1)
16/16
1)

Other manuals for Fronius Primo 10.0-1 208-240