The breakaway PC board of the new 
RECERBO must also be removed and 
returned with the faulty RECERBO to 
Fronius.
Insert the previously separated brea-
kaway PC board (4) on the internal 
side of the new RECERBO.
Mount the RECERBO holder (3) on the 
new RECERBO
- thread the wire up
- press down.
Insert the new RECERBO assembly
The locks (2) on the RECERBO holder 
must be fully engaged in the housing 
frame
Insert the external fan cable in the cab-
ling (1)
Insert the Datamanager card, close the 
inverter and insert into the wall bracket 
(see "Replacing the Datamanager 
Card" and "Opening and Closing De-
vice" sections)
(4) (3)
NOTE! If the breakaway PC board 
is forgotten or not inserted correct-
ly, the inverter will show a status 
code (482) on the display.
NOTE! All guide pins and bolts 
must be engaged.