17
EN
If overlength AC or DC cables are to be laid
in loops in the connection area, attach the
cables with cable ties to the eyelets provi-
ded on the top and bottom of the connecti-
on block.
Maximum fuse
rating on alternat-
ing current side
max. C 25 A
AC ~
Inverter Phases AC power Maximum
fuse rating
Recommend-
ed fuse rating
Fronius Symo 3.0-3-S / -M 3 3000 W C 25 A C 10 A
Fronius Symo 3.7-3-S / -M 3 3700 W C 25 A C 13 A
Fronius Symo 4.5-3-S / -M 3 4500 W C 25 A C 16 A
Fronius Symo 5.0-3-M 3 5000 W C 25 A C 16 A
Fronius Symo 6.0-3-M 3 6000 W C 25 A C 16 A
Fronius Symo 7.0-3-M 3 7000 W C 25 A C 20 A
Fronius Symo 8.2-3-M 3 8200 W C 25 A C 25 A