AC output data Full Backup
Nominal mains voltage
1 ~ NPE 220 V
1 ~ NPE 230 V
1 ~ NPE 240 V
Nominal frequency for Full Backup
53 / 63 Hz
1)
Switching time < 90 s
Power factor cos phi
2)
0 - 1
General data
Maximum efficiency 97.6%
European efficiency (U
mpp nom
) 96.8%
European efficiency (U
mpp max
) 95.9%
European efficiency (U
mpp min
) 95.3%
Self-consumption at night 8.2 W
Cooling Controlled forced-air ventilation
Protection class IP 66
Dimensions H x W x D 530 × 474 × 165 mm
Weight 17 kg
Inverter topology Non-insulated transformerless
Permitted ambient temperature -40 °C – +60 °C
Permissible humidity 0 - 100% (incl. condensation)
EMC emission class B
DC/AC overvoltage category
(in accordance with IEC 62109-1)
2 / 3
Pollution degree 2
Sound pressure 42 dB(A) (ref. 20µPa)
Safety class (according to IEC62103) 1
Protection devices
DC isolation measurement
11)
Warning / shutdown at R
ISO
<
100 kOHM
Overload performance Operating point shift, power limiter
DC disconnector Integrated
RCMU
11)
Integrated
RCMU classification The software class of the safety plat-
form(s) is specified as a class B con-
trol function (single channel with peri-
odic self-test) according to IEC60730
Annex H.
Active anti-islanding method Frequency conversion method
AFCI Integrated