Cables with the following design can be connected to the terminals of the invert-
er:
-
Copper: round, solid
-
Copper: round, fine-stranded, up to conductor class 4
Grid connections with push-in terminal*
Select a sufficiently large cable cross section based on the actual device output!
Power
categories
Solid Multi-stranded Fine-stranded
Fine-stranded with ferrules‐
with/without collar
3 - 6 kW
(3-pin)
2.5 - 10 mm
2
AWG 14-8
2.5 - 10 mm
2
AWG 14-8
2.5 - 10 mm
2
AWG 14-8
2.5 - 6 mm
2
AWG 14-10
Grid connections backup power with push-in terminal*
Select a sufficiently large cable cross section based on the actual device output.
Power
categories
Solid Multi-stranded Fine-stranded
Fine-stranded with ferrules‐
with/without collar
3 - 6 kW
(3-pin)
1.5 - 10 mm
2
AWG 16-8
1.5 - 10 mm
2
AWG 16-8
1.5 - 10 mm
2
AWG 16-8
1.5 - 6 mm
2
AWG 16-10
PV/BAT connections with push-in terminal**
Select a sufficiently large cable cross section based on the actual device output.
Power
categories
Solid Multi-stranded Fine-stranded
Fine-stranded with ferrules‐
with/without collar
3 - 6 kW
(2 x 5-pin)
4 - 10 mm
2
AWG 12-8
4 - 10 mm
2
AWG 12-8
4 - 10 mm
2
AWG 12-8
4 - 6 mm
2
AWG 12-10
Ground electrode terminal (6-pin)
Select a sufficiently large cable cross section based on the actual device output.
Number of
pins
Solid Multi-stranded Fine-stranded
Fine-stranded with ferrules‐
with/without collar
2
2.5 - 16 mm
2
AWG 14-6
2.5 - 16 mm
2
AWG 14-6
2.5 - 16 mm
2
AWG 14-6
2.5 - 16 mm
2
AWG 14-6
4
2.5 - 10 mm
2
AWG 14-8
2.5 - 10 mm
2
AWG 14-8
2.5 - 10 mm
2
AWG 14-8
2.5 - 10 mm
2
AWG 14-8
* According to product standard IEC 62109, the ground conductor must
correspond to the phase cross-section for phase cross-sections ≤16 mm²;
for phase cross-sections >16 mm², it must correspond to at least 16 mm².
** The cable cross section must be dimensioned in accordance with the in-
stallation situation and the specifications of the battery manufacturer.