Loading...
Conformity to UL standards and Canadian standards cUL certification
Short circuit rating
When protected by class J fuses, suitable for use on a circuit capable of delivering not more
than B rms symmetrical amperes, A volts maximum.
Power
supply
voltage
Inverter type
Power supply max. voltage
Volts
Power supply current
Amperes
FRN0025C2S-2U
FRN0033C2S-2U
FRN0047C2S-2U
Three-phase
200V
FRN0060C2S-2U
240VAC 100,000 A or less
FRN0013C2S-4U
FRN0018C2S-4U
FRN0024C2S-4U
Three-phase
400V
FRN0030C2S-4U
480VAC 100,000 A or less
5. Install UL certified fuses rated 600Vac between the power supply and the inverter, referring to
the table below.
Required torque
Ib-in (N
m)
Wire size
AWG or kcmil(mm
2
)
Control circuit Control circuit
Power
supply
voltage
Inverter type
Main
terminal
*1
TERM1
*2
TERM2-1
TERM2-2
*3
Main
terminal
*1
TERM1
*2
TERM2-1
TERM2-2
Class J fuse cur-
rent(A)
FRN0025C2S-2U 60
FRN0033C2S-2U
27
(3.0)
8
(8.4)
75
FRN0047C2S2U
6
(13.3)
100
Three-phase
200V
FRN0060C2S-2U
51.3
(5.8)
3.5
(0.4)
1.7
(0.2)
4
(21.2)
6
(13.3)
20
(0.5)
150
FRN0013C2S-4U
12
(3.3)
10
(5.3)
30
FRN0018C2S-4U
27
(3.0)
10
(5.3)
40
FRN0024C2S-4U 60
Three-phase
400V
FRN0030C2S-4U
51.3
(5.8)
3.5
(0.4)
1.7
(0.2)
8
(8.4)
20
(0.5)
70
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com