Chapter 2 MOUNTING AND WIRING OF THE INVERTER
2.3.2 Terminal arrangement and screw specifications
(1) Arrangement of the main circuit terminals
Table 2.3 Main Circuit Terminals
Power
supply
voltage
Nominal ap-
plied motor
(HP)
Inverter type
Terminal
screw size
Tightening
torque
(lb-in)
Refer to:
7.5 FRN0025C2S-2U
10 FRN0033C2S-2U
M5 26.6 Figure E
15 FRN0047C2S-2U
Three-
phase
200 V
20 FRN0060C2S-2U
M6
51.3
Figure
F
7.5 FRN0013C2S-4U
10 FRN0018C2S-4U
M5 26.6 Figure E
15 FRN0024C2S-4U
Three-
phase
400 V
20 FRN0030C2S-4U
M6
51.3 Figure F
Figure E
Figure F
2.3.3 Recommended wire sizes
Table 2.6 lists the recommended wire sizes. The recommended wire sizes for the main circuit ter-
minals for an ambient temperature of 50
C are indicated for two types of wire: HIV single wire (for the
maximum allowable temperature 75°C) (before a slash (/)) and IV single wire (for 60°C) (after a slash
(/))
Table 2.6 Recommended Wire Sizes
Recommended wire size (AWG ) *1
Main circuit
Main circuit power input
[L1/R, L2/S, L3/T]
[L1/L, L2/N]
Grounding [
G]
Power supply voltage
Nomi-
nal
applied
motor
(HP)
Inverter type
w/ DCR
*2
w/o DCR
Inverter
output
[U, V, W]
DCR
[P1, P (+)]
Braking
resistor
[P (+), DB]
Control
circuit
7.5
FRN0025C2S-2U
14/10 12/ 8 12/10 12/10
10
FRN0033C2S-2U
12/ 8 10/ 6 12 /8 10/ 6
15
FRN0047C2S-2U
10/ 6 6/ 4 8/ 6 8/ 4
Three-phase
200 V
20
FRN0060C2S-2U
6/ 4 4/ 2 6/ 4 6/ 2
14/14
20
16