Parameter
Function Setting range ,QLWLDOYDOXH 5HPDUNV
ʋ 'LVSOD\ Name
530
PV input type Sets the type of input sensor JPT1: 0.0 to 150.0°C
JPT2: 0.0 to 300.0°C
JPT3: 0.0 to 500.0°C
-37WR&
JPT5: -50.0 to 100.0°C
JPT6: -100.0 to 200.0°C
-37WR&
PT1: 0.0 to 150.0°C
PT2: 0.0 to 300.0°C
PT3: 0.0 to 500.0°C
37WR&
PT5: -50.0 to 100.0°C
PT6: -100.0 to 200.0°C
37WR&
37WR&
-WR&
-WR&
-WR&
-WR&
.WR&
K2: -20.0 to 500.0°C
.WR&
.WR&
5WR&
%WR&
6WR&
T1: -199.9 to 200.0°C
37WR&
(WR&
(WR&
(WR&
/WR&
8WR&
8WR&
1WR&
W: 0 to 2300°C
3/WR&
0-5 V: 0 to 5 V
1-5 V: 1 to 5 V
0-10: 0 to 10 V
2-10: 2 to 10 V
MV: 0 to 100 mV
WRP$
WRP$
K1 [RESET]
Refer to section 10 for the detail.
531
PV input lower limit Sets the lower limit of PV input -1999 to 9999 0 [RESET]
532
PV input upper limit Sets the upper limit of PV input -1999 to 9999 [RESET]
533
'HFLPDOSRLQWSRVLWLRQ 6HWVWKHGHFLPDOSRLQWSRVLWLRQIRUWKH3969 1RGLJLWDIWHUGHFLPDOSRLQW
1: 1 digit after decimal point
2: 2 digit after decimal point
3: 3 digit after decimal point
0 [RESET]
535
6TXDUHURRWH[WUDFWRUFXWSRLQW Sets the cut point for square root calculation. -0.1 to 105.0(%) -0.1%
536 PV input shift Sets the amount of shift for PV input -10 to 10%FS 0.00%FS
39LQSXW¿OWHU 6HWVWKHWLPHFRQVWDQWIRUWKH39LQSXW¿OWHU 0.0 to 120.0 sec 5.0 sec
Remote SV zero adjustment $GMXVWVWKH]HURVLGHRIUHPRWH69 -50 to 50%FS 0.00%FS
Remote SV span adjustment $GMXVWVWKHVSDQVLGHRIUHPRWH69 -50 to 50%FS 0.00%FS
Remote SV input range Sets the range for remote SV input. 0-5v: 0 to 5 V
1-5v: 1 to 5 V
0-10: 0 to 10 V
2-10: 2 to 10 V
1-5V
5HPRWH69LQSXW¿OWHU 6HWVWKHWLPHFRQVWDQWIRUWKH569LQSXW¿OWHU 0.0 to 120.0 s 0.0 s
OUT1 range Sets the range of the control output 1(OUT1) 0-5v: 0 to 5 V
1-5v: 1 to 5 V
0-10: 0 to 10 V
2-10: 2 to 10 V
WRP$
WRP$
0-10 (voltage)
FXUUHQW
'LVSOD\HGZKHQ287LVFXUUHQWRUYROWDJHRXWSXW
OUT2 range Sets the range of the control output 2(OUT2) 0-5v: 0 to 5 V
1-5v: 1 to 5 V
0-10: 0 to 10 V
2-10: 2 to 10 V
WRP$
WRP$
0-10 (voltage)
FXUUHQW
'LVSOD\HGZKHQ287LVFXUUHQWRUYROWDJHRXWSXW
09GXULQJ)$/7 Sets the output value for the control output (MV1) during
)$/7
-5.0 to 105.0% -5.0%
550 09GXULQJ)$/7 Sets the output value for the control output (MV2) during
)$/7
-5.0 to 105.0% -5.0%
551 MV1 during Soft Start Sets the value for the control output (MV1) during soft start -5.0 to 105.0% 105.0%
553 Soft Start set time 6HWVWKHWLPHIURPVWDUWXSWRWKH¿QLVKRIVRIWVWDUW 00:00 to 99:59 (hour:min) 00:00 Be sure to set 0.00 during dual control.
MV1 during standby Sets the value for the control output (MV1) during standby -5.0 to 105.0% -5.0%
555 MV2 during standby Sets the value for the control output (MV2) during standby -5.0 to 105.0% -5.0%
556 Standby mode 6HWVRQRIIRIWKHDODUPRXWSXWGXULQJVWDQGE\ $/0 2))$2 21
$/0 21$2 21
$/0 2))$2 2))
$/0 21$2 2))
0 [RESET]
$2 Selects what to transfer to the analog output. PV
SV
MV
'9
PFb
PV
$2ORZHUVFDOLQJ 6HWVWKH$2ORZHUVFDOLQJ -100.0 to 100.0% 0.0%
559
$2XSSHUVFDOLQJ 6HWVWKH$2XSSHUVFDOLQJ -100.0 to 100.0% 100.0%
561
)L[HGYROWDJHYDOXH Sets the voltage for calculating electric power 1 to 500V 100 (100 V)
562 Current value for simple power
calculation
Sets the current value for simple power calculation WR$ $
'HFLDOSRLQWSRVLWLRQIRUHOHFWULFSRZHU Sets the position of decimal point for calculationed power
consumption.
0 : 0
1 : 0.1
2 : 0.01
3 : 0.001
1 : 0.1 'RQRWFKDQJHLWGXULQJFDOFXODWLRQ
565
Power factor for simple calculation Sets the power factor for simple calculation 0.00 to 1.00 1.00
566 Upper limit of relay contact operation Sets the upper limit on the number of times a relay contact
can operate. If you set it to 0, no alarm will be generated.
0 to 9999 100
(100,000 times)
Upper limit of operating days Sets the upper limit on the number of days the device
operates. If you set it to 0, no alarm will be generated.
0 to 5000 3650 (3650 days)