ā 53 ā
7
Chapter
System (Ch7)
"
FF
FF
LL
LL
oo
oo
11
11
"
FLo1 Output 1 set value during
FALT
01A1
H
40390 41390 Word -300 to 10300
(-3.00 to 103.00%)
"
FF
FF
LL
LL
oo
oo
22
22
"
FLo2 Output 2 set value during
FALT
01A2
H
40391 41391 Word -300 to 10300
(-3.00 to 103.00%)
"
SS
SS
ff
ff
oo
oo
11
11
"
Sfo1 Soft start OUT1
set value
01A3
H
40392 41392 Word -300 to 10300
(-3.00 to 103.00%)
"
SS
SS
FF
FF
TT
TT
MM
MM
"
SFTM Soft start set time 01A5
H
40394 41394 Word 00:00 to 99:59 (hour:min) 00:00 (hour:min)
"
SS
SS
bb
bb
oo
oo
11
11
"
Sbo1 During standby, OUT1
set value
01A9
H
40398 41398 Word -300 to 10300
(-3.00 to 103.00%)
"
SS
SS
bb
bb
oo
oo
22
22
"
Sbo2 During standby, OUT2
set value
01AA
H
40399 41399 Word -300 to 10300
(-3.00 to 103.00%)
"
SS
SS
bb
bb
MM
MM
dd
dd
"
SBMD Standby mode setting 01AB
H
40400 41400 Word 0 to 3 0
"
AA
AA
oo
oo
TT
TT
"
AOTTypes of AO output 01AC
H
40401 41401 Word 0: PV
1: SV
2: MV
3: DV
4: PFB
PV
"
AA
AA
oo
oo
LL
LL
"
AoL AO lower limit scaling 0082
H
40115 41115 Word -100% to 100%FS 0%
"
AA
AA
oo
oo
hh
hh
"
Aoh AO upper limit scaling 0083
H
40116 41116 Word -100% to 100%FS 100%
Parameter
display
Parameter
name
Contents
Relative
address
Resistor Number
Type
Read data
Written data
range
Factory Setting
Dependent
on range
Internal
Engineering
unit
"
UU
UU
KK
KK
EE
EE
YY
YY
"
UKEY USER key
assignment settings
009C
H
40141 41141 Word 0 (no function)
1 (Switches between STBY ON/OFF)
2 (Switches between Auto/Manual)
3 (Switches between Local/Remote)
4 (Switches EXMV)
5 (Starts AT (standard))
6 (Starts AT (low PV))
7 (no function)
8 (Ramp SV HOLD)
9 (Ramp/soak RUN/OFF)
10
(Ramp/soak RUN/HOLD)
11 (no function)
12 (Latch cancel (all))
13 (Latch cancel (DO1))
14 (Latch cancel (DO2))
15 (Latch cancel (DO3))
16 (Latch cancel (DO4))
17 (Latch cancel (DO5))
18 (Start timer (DO1))
19 (Start timer (DO2))
20 (Start timer (DO3))
21 (Start timer (DO4))
22 (Start timer (DO5))
23 (SV No. + 1 (send))
24 (PID No. + 1 (send))
25 (no function)
26
(Pattern No. + 1 (send))
27 (SV No. + 1, PID No. + 1 (send))
2
Parameter
display
Parameter
name
Contents
Relative
address
Resistor Number
Type
Read data
Written data
range
Factory Setting
Dependent
on range
Internal
Engineering
unit