8-2. External output
Use an external output cable with appropriate external dimension, depending on the number of ca-
bles to be installed.
A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25 m).
Output voltage: High DC 12 V ± 2 V, Low 0 V.
Permissible current: 50 mA
For details, refer to "Combination of external input and output" on page 28.
When indicator, etc. are connected directly
Example: Function setting 60 is set to "00"
1
2
CN47
LED
PCB
Resistor
Connected unit
+
-
When connecting with a device equipped with a power supply
Example:
Function setting 60 is set to "00"
1
2
Connected device
CN47
PCB
Connected unit Relay
(Operation status)
-
+
- 26 -
8-2. External output 8. External input and output
CASSETTE TYPE
ADUH09-18LUAS1
CASSETTE TYPE
ADUH09-18LUAS1