EasyManua.ls Logo

Fujitsu ACUH09LUAS1 - Capacity Compensation Rate for Pipe Length and Height Difference; Model: AOUH09 LUAS1

Fujitsu ACUH09LUAS1
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H H
6-1. Model: AOUH09LUAS1
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length
m
5 7.5 10 15 20
ft 16 25 33 49 66
Height difference H
Indoor unit is higher than outdoor
unit *1
15 49 0.883 0.893
10 33 0.956 0.897 0.907
7.5 25 0.988 0.960 0.901 0.910
5 16 1.021 0.992 0.964 0.904 0.915
0 0 1.029 1.000 0.971 0.913 0.922
Indoor unit is lower than outdoor
unit *2
-5 -16 1.029 1.000 0.971 0.913 0.922
-7.5 -25 1.000 0.971 0.913 0.922
-10 -33 0.971 0.913 0.922
-15 -49 0.913 0.922
HEATING
Pipe length
m
5 7.5 10 15 20
ft 16 25 33 49 66
Height difference H
Indoor unit is higher than outdoor
unit *1
15 49 - - - 0.901 0.884
10 33 - - 0.974 0.901 0.884
7.5 25 - 1.000 0.974 0.901 0.884
5 16 1.006 1.000 0.974 0.901 0.884
0 0 1.006 1.000 0.974 0.901 0.884
Indoor unit is lower than outdoor
unit *2
-5 -16 1.001 0.995 0.969 0.896 0.880
-7.5 -25 - 0.993 0.967 0.894 0.878
-10 -33 - - 0.965 0.892 0.876
-15 -49 - - - 0.883 0.867
- 82 -
6-1. Model: AOUH09LUAS1 6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOUH09-18LUAS1
OUTDOOR UNIT
AOUH09-18LUAS1

Table of Contents

Other manuals for Fujitsu ACUH09LUAS1

Related product manuals