7. Additional charge calculation
7-1. Model: AOUH09LUAS1
Refrigerant type R410A
Refrigerant amount
lb oz 2lbs.3oz.
g 1,000
¢ Refrigerant charge
Total pipe length
ft 49 or less 66 (Max.)
0.2 oz/ft
(20 g/m)
m 15 or less 20 (Max.)
Additional charge
oz 0 4.0
g 0 100
7-2. Model: AOUH12LUAS1
Refrigerant type R410A
Refrigerant amount
lb oz 2lbs.10oz.
g 1,200
¢ Refrigerant charge
Total pipe length
ft 49 or less 66 (Max.)
0.2 oz/ft
(20 g/m)
m 15 or less 20 (Max.)
Additional charge
oz 0 4.0
g 0 100
7-3. Model: AOUH18LUAS1
Refrigerant type R410A
Refrigerant amount
lb oz 2lbs.12oz.
g 1,250
¢ Refrigerant charge
Total pipe length
ft 66 or less 82 or less 98 (Max.)
0.2 oz/ft
(20 g/m)
m 20 or less 25 or less 30 (Max.)
Additional charge
oz 0 4.0 7.0
g 0 100 200
- 85 -