Check Point : ARXC36LATH (High Static Pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Red Violet
Violet Blue
Red Black
White Red
Lead wire
13.4 8%
16.9 8%
11.5 8%
13.3 8%
Resistance value
(AC)
Thermal protector
Pr
VIOLET (Med)
BLUE (Low)
RED (Hi)
BLACK
WHITE
150°C
at 20°C
Check Point : ARXC45/ 60LATH (High Static Pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Red Violet
Violet Blue
Red Black
White Red
Lead wire
6.84 7%
9.78 7%
6.1 7%
6.1 7%
Resistance value
(AC)
Thermal protector
Pr
VIOLET (Med)
BLUE (Low)
RED (Hi)
BLACK
WHITE
145°C
at 20°C
Check Point : ARXC72LATH (High Static Pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
(AC)
Thermal protector
Pr
VIOLET (Low)
BLUE (S-Lo)
PINK (Med)
RED (Hi)
BLACK
WHITE
145°C
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Lead wire
5.25 7%
5.02 7%
0.94 7%
1.86 7%
0.94 7%
Resistance value
at 20°C
Check Point : ARXC90LATH (High Static Pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
(AC)
Thermal protector
Pr
VIOLET (Low)
BLUE (S-Lo)
PINK (Med)
RED (Hi)
BLACK
WHITE
145°C
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Lead wire
4.24 7%
4.16 7%
0.46 7%
0.46 7%
0.91 7%
Resistance value
at 20°C