Check Point : AS A18 / 24 / 30 LATH(Wall Mounted Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
(AC)
BLUE (Low)
YELLOW
RED (Hi)
BLACK
WHITE
Thermal protector
140°C
Blue Red
Blue Black
White Red
Lead wire
134 8%
25.5 8%
306 8%
Resistance value
at 20°C
Pr
04-103