06-11
Thermistor (comp.temp.)
Cut the Discharge pipe in this range.
Cut the Oil balance pipe in this range.
Cut the Suction pipe in this range.
[REFERENCE DATA]
Model : AJY126LALF (2 compressor model)
Constant speed Comp.
TERMINAL
[ U : RED, W : BLACK, V : WHITE ]
Range
Range
Range
Oil balance pipe
Thermistor (Discharge)
Crank Case Heater
Caution
Keep their shape better.
There is a possibility of catching fire to oil when removing
by the welding without cutting it.
Caution
Oil flows out when piping is cut when a lot of oil remains.
So receive oil with the rag etc.
Procedure for compressor installation.
Reverse procedure to removing the compressor.
Precautions for installation of Compressor.
(1) When brazing, do not apply the flame to the terminal.
(2) When brazing, be sure to replace the air in the pipe with nitrogen gas to prevent forming oxidization scale.