6. SYSTEM DESIGN
4) Static pressure
Select appropriate static pressure according to the installation conditions.
(
... Factory setting)
Setting description Function number Setting value
0 in.WG (0 Pa)
26
00
0.04 in.WG (10 Pa) 01
0.08 in.WG (20 Pa) 02
0.12 in.WG (30 Pa) 03
0.16 in.WG (40 Pa) 04
0.20 in.WG (50 Pa) 05
0.24 in.WG (60 Pa) 06
0.28 in.WG (70 Pa) 07
0.32 in.WG (80 Pa) 08
0.36 in.WG (90 Pa) 09
0.10 in.WG (25 Pa) [Standard] 31
Range of static pressure is different from one model to other.
Model name Range of static pressure
ARU9RLF
0 to 0.36 in.WG (0 to 90 Pa)ARU12RLF
ARU18RLF
ARU24RLF 0 to 0.20 in.WG (0 to 50 Pa)
5) Cooler room temperature correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be selected as shown in the table below.
(
... Factory setting)
Setting description Function number Setting value
Standard
30
00
Slightly lower control 01
Lower control 02
Warmer control 03
When using floor console installation, change the setting value to “01” (Only Slim duct type).
6) Heater room temperature correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be changed as shown in the table below.
(
... Factory setting)
Setting description Function number Setting value
Standard
31
00
Lower control 01
Slightly warmer control 02
Warmer control 03
When using floor console installation, change the setting value to “01” (Only Slim duct type).
7) Auto restart
Enable or disable automatic system restart after a power outage.
(
... Factory setting)
Setting description Function number Setting value
Yes
40
00
No 01
* Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, or external input device.