6. SYSTEM DESIGN
8) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller
temperature sensor.
(
... Factory setting)
Setting description Function number Setting value
No
42
00
Yes 01
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote controller
unit sensor.
9) Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
(
... Factory setting)
Setting description Function number Setting value
A
44
00
B01
C02
D03
10) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(
... Factory setting)
Setting description Function number Setting value
Operation/Stop mode
46
00
(Setting forbidden) 01
Forced stop mode 02
- (06 - 70) -
SYSTEM
DESIGN
SYSTEM
DESIGN